STUDI ALIRAN DAYA TIGA FASA DENGAN PENEMPATAN STEP VOLTAGE REGULATOR HUBUNG WYE PADA PENYULANG PAKIS GI MENGGALA

FANNY SIMATUPANG, 1115031076 (2016) STUDI ALIRAN DAYA TIGA FASA DENGAN PENEMPATAN STEP VOLTAGE REGULATOR HUBUNG WYE PADA PENYULANG PAKIS GI MENGGALA. UNIVERSITAS LAMPUNG, FAKULTAS TEKNIK.

[img]
Preview
File PDF
ABSTRAK (ABSTRACT).pdf

Download (12Kb) | Preview
[img] File PDF
SKRIPSI FULL.pdf
Restricted to Hanya pengguna terdaftar

Download (4070Kb)
[img]
Preview
File PDF
SKRIPSI TANPA BAB PEMBAHASAN.pdf

Download (4070Kb) | Preview

Abstrak (Berisi Bastraknya saja, Judul dan Nama Tidak Boleh di Masukan)

Panjangnya saluran distribusi menyebabkan profil tegangan yang rendah. Untuk mengatasi masalah tersebut, dengan memasang Step Voltage Regulator (SVR). SVR dapat dipasang dengan menggunakan hubung wye atau hubung delta pada jaringan distribusi. Dalam hal ini SVR menggunakan analisis aliran daya tiga fasa dengan hubung wye. Pada sistem distribusi Lampung, SVR tipe B yang digunakan untuk pekerjaan ini dan tipe ini umumnya sering ditemukan. Model yang dikembangkan dan digunakan dalam perangkat lunak analisis aliran daya tiga fasa pada bahasa pemprograman pyton berdasarkan metode Newton-Raphson. Pada jaringan 20 kV, penyulang Pakis pada Gardu Induk Menggala biasa digunakan untuk pengujian dalam pengembangan model. Penyulang ini memikul beban dari tegangan jatuh sepanjang saluran maka dari itu diperlukan pemasangan SVR untuk meningkatkan profil tegangannya. Hasil dari penelitian ini kemudian dibandingkan dengan kasus yang sama dengan OpenDSS dari Electric Power Research Institute. Beban setimbang dan tak setimbang di pertimbangkan dalam penelitian ini. Hasil menunjukkan dengan pemasangan SVR ± 10% dapat memperbaiki profil tegangan. Perbandingan dengan OpenDSS juga menunjukkan hasil yang sama dengan perangkat lunak yang dikembangkan yaitu UnilaPF. Kata Kunci : Step Voltage Regulator (SVR), Tegangan, UnilaPF, OpenDSS, GI Menggala. ABSTRACT A long distribution feeder may experience poor voltage profile. In order to correct this problem, a step voltage regulator (SVR) can be installed. SVR can be installed in either Delta or Wye connection to the distribution network. This work addresses SVR with Wye connection model for a three-phase power flow analysis. Type-B SVR is considered in this work as this type is commonly found the distribution system in Lampung Province. The developed model is then implemented in a three-phase power flor analysis software written in Python Programming Language based on Newton-Raphson method. An actual 20 kV, Pakis Feeder of Menggala Substation is used to examine the developed model. This feeder suffers from high voltage drop along the line and hence installation of SVR should improve its voltage profile. Results are then compared with similar case calculated by OpenDSS of Electric Power Research Institute. Both balanced and unbalanced loads are considered in this work. Results show that voltage profile is improved after installation of SVR of about ± 10%. Comparison with OpenDSS also reveals that the developed software produces similar results with UnilaPF. Kata Kunci : Step Voltage Regulator (SVR), Voltage, UnilaPF, OpenDSS,Wye, Menggala Substation.

Jenis Karya Akhir: Skripsi
Subyek: > Teknik Elektro. Rekayasa elektronik Nuklir
> Teknik Elektro. Rekayasa elektronik Nuklir
Program Studi: Fakultas Teknik > Prodi S1-Teknik Elektro
Pengguna Deposit: 8991347 . Digilib
Date Deposited: 29 Aug 2016 03:33
Terakhir diubah: 29 Aug 2016 03:33
URI: http://digilib.unila.ac.id/id/eprint/23739

Actions (login required)

Lihat Karya Akhir Lihat Karya Akhir