<> "The repository administrator has not yet configured an RDF license."^^ . <> . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG"^^ . "ABSTRACT\r\n\r\nActive thermography testing is one of the non-destructive tests that uses an \r\ninfrared camera as a recorder and produces a thermogram. Thermogram is an \r\ninterpretation of the heat energy received by the infrared camera thermal sensor \r\nwhich still contains noise. Reflected temperature (Trefl) is one of the noise that \r\narises from active thermography testing and will be used as a correction value. \r\nThis research presents a method to finding the position of thermocouple \r\ninstallation around the heat source, so that the temperature values at that position \r\nare used as the Trefl value to correct noise in the thermogram. Cube-shaped \r\nconcrete samples with a size of 10x10x15 cm were measured using \r\nthermocouples and infrared cameras as far as 1 meter, 2 meters, and 3 meters. \r\nThe results showed the difference in measurement results using thermocouples \r\nand thermography of 2,3499 ℃; 3,0246 ℃; and 3,0946 ℃, then the average \r\nTrefl value obtained from active thermography testing was 51,6496 ℃; 57,9544 \r\n℃; and 59,7707 ℃ with the thermocouple located 5 cm in front of the halogen \r\nlamp and the average distance obtained by Trefl from the top of the grid board \r\nwas 13 cm; 18 cm; and 19 cm. The average difference between the data before \r\ncorrection and the measurement data is 2,7385 ℃; 3,3749 ℃; and 3,4818 ℃, \r\nrespectively, then after the analysis of the calculation of the temperature \r\ndifference with the measurement results has decreased, namely 0,4634℃; \r\n1,4829℃; and 0,4666℃ with the analysis of the error (ΔTerr) on average \r\nobtained 1,4479%; 4,3587%; 1,3187%. Based on the analysis results, the \r\naccuracy of the error data is good because the average value of error analysis \r\n(ΔTerr) <5%. This research cannot be done deterministically.\r\nKeywords : Reflected Temperature, Active thermography, Non-destructive \r\nTesting\r\n\r\nABSTRACT\r\n\r\nPengujian termografi aktif merupakan salah satu pengujian non-destruktif yang \r\nmenggunakan kamera inframerah sebagai perekam dan menghasilkan \r\ntermogram. Termogram merupakan interpretasi energi panas yang diterima oleh \r\nsensor termal kamera inframerah yang masih mengandung noise. Reflected \r\ntemperature (Trefl) merupakan salah satu noise yang muncul dari pengujian \r\ntermografi aktif dan akan digunakan sebagai nilai koreksi. Penelitian ini \r\nmenyajikan suatu metode untuk mencari posisi pemasangan termokopel di \r\nsekitar sumber panas, sehingga nilai suhu pada posisi tersebut digunakan sebagai \r\nnilai Trefl untuk memperbaiki noise pada termogram. Sampel beton berbentuk \r\nkubus dengan ukuran 10x10x15 cm diukur suhu permukaannya menggunakan \r\ntermokopel dan kamera inframerah sejauh 1 meter, 2 meter, dan 3 meter. Hasil \r\npenelitian menunjukkan selisih hasil pengukuran menggunakan termokopel dan \r\ntermografi sebesar 2,3499 ℃; 3,0246 ℃; dan 3,0946 ℃, lalu rata-rata nilai Trefl\r\nyang didapatkan dari pengujian termografi aktif sebesar 51,6496℃; 57,9544℃; \r\ndan 59,7707℃ dengan termokopel terletak 5 cm di depan lampu halogen dan \r\njarak rata-rata yang didapatkan Trefl dari atas papan grid sebesar 13 cm; 18 cm; \r\ndan 19 cm. Selisih rata-rata antara data sebelum dikoreksi dan data hasil \r\npengukuran berturut-turut sebesar 2,7385℃; 3,3749℃; dan 3,4818℃, lalu \r\nsetelah dilakukan analisis perhitungan selisih suhu dengan hasil pengukuran \r\nmengalami penurunan yaitu berturut-turut sebesar 0,4634℃; 1,4829℃; dan \r\n0,4666℃ dengan analisis kesalahan (ΔTerr) rata-rata didapatkan 1,4479%; \r\n4,3587%; 1,3187%. Berdasarkan hasil analisis terebut menunjukkan akurasi data \r\nkesalahan tergolong bagus karena nilai rata-rata analisis kesalahan (ΔTerr)<5%.\r\nUntuk penelitian ini tidak bisa dilakukan secara deterministik.\r\nKeywords : Reflected Temperature, Termografi aktif, Pengujian Non-destruktif\r\n"^^ . "2023-11-09" . . . . . "TEKNIK"^^ . . . . . . . " FAUZAN IKROMI"^^ . "MUHAMMAD"^^ . " FAUZAN IKROMI MUHAMMAD"^^ . . "UNIVERSITAS LAMPUNG"^^ . . . . . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (File PDF)"^^ . . . "ABSTRAK.pdf"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (File PDF)"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (File PDF)"^^ . . . "SKRIPSI TANPA BAB IV.pdf"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "lightbox.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "preview.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "medium.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "small.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "indexcodes.txt"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "indexcodes.txt"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "lightbox.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "preview.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "medium.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "small.jpg"^^ . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . . "PENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE\r\nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \r\nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG (Other)"^^ . . . . . "HTML Summary of #76947 \n\nPENENTUAN LETAK PENGUKURAN REFLECTED TEMPERATURE \nDENGAN MENGGUNAKAN TERMOKOPEL PADA PENGUJIAN \nTERMOGRAFI AKTIF TERHADAP BETON BERTULANG\n\n" . "text/html" . . . "690 Pembangunan gedung" . .